New Written Questions
Quiz Summary
0 of 30 Questions completed
Questions:
Information
You have already completed the quiz before. Hence you can not start it again.
Quiz is loading…
You must sign in or sign up to start the quiz.
You must first complete the following:
Results
Results
Your time:
Time has elapsed
Categories
- Not categorized 0%
-
Answers
Question 1
Page 40 – 2.6.2 (d) GN 3
When carrying out an Initial verification after completing a new installation or installaing a new circuit, 100 % of circuits and components need inspecting and testing. When completing an EICR, sampling will be considered which will produce limitations on the Certificate.
Question 2
If the property was sold
It is required for securing a mortgage
Inspections in the future
Comply to the Construction, Design and Management Regulation CDM
Insurance purposesQuestion 3
Page 121 GN 3
Designer
Construction Manager
Person responsible for the Inspection and testing.Question 4
Ask for permission, locate main switch and switch off
Lock off, key in pocket and hang a warning sign
Prove Approved Voltage Indicator on a Proving unit
Test dead across L-N, L-E, N-E
Re-prove Approved Voltage Indicator on a Proving unitQuestion 5
Anyone that is in the area of the electrical installation including the Inspector, Customers, public and other trades
Electric shock could be recieved by any of the listed parties due to live parts exposed.
Circuits could be unintentionally energised causing harm to anyone testing the circuitQuestion 6
Part 715 BS7671
Items – Lighting, fans, Hand lamps and chargers
Locations – Bath or shower, swimming pools, saunas
Inspections – Condition of cables, Transformer specification, connections, Environmental conditionsQuestion 7
Regulation BS7671 – 537.3.2
Items – Multipole switch, Circuit breaker, control and protective switching device (CPS), control switch operating a contractor, plug and socket outlet
Locations – Local to the load
Inspections – Location of device – Supervision or be able to be locked in the off position, rated for the intended load, connections and IP ratingsQuestion 8
1) C3 – 521.10 BS7671
2) C2 – 434.5 BS7671
3) FI – Page 104 GN 3
4) C3 – 514.13 BS7671Question 9
Page 40 GN 3
Repair or replace the item to ensure it meets the requirements of BS7671/specification and then re inspect.
Question 10
Page 25 GN 3
Protected against contact with a finger and objects such as barriers or enclosures > 12mm diameter
Question 11
Page 25 GN 3
Protected against contact with small objects or the horizontal top surfaces of items > 1mm diameter
Question 12
Page 92 GN 3
Repair or replace the item so it meets the specification requirements if possible, or report in writing to the customer immediately if the item can not be repaired or replaced at that time.
Question 13
Item to comply to GS38 – Instrument test leads when testing Live
Requirements of GS38
– 2-4mm tips
– Finger guards
– Robust, sheathed and flexible leads
– Fused Leads
– No damageQuestion 14
Page 41 GN 3
Periodic Inspection and Testing is carried out following a sampled selection
An Initial Verification is carried out on 100% of a new and untested circuit
Existing installations should have been tested previously
A result recorded for a test on an Initial Verification may rely on the previous test resultQuestion 15
Page 43 GN 3
Length
Size of conductor (CSA)
Material (Resistivity)
Temperature
External Influences such as Thermal Insulation and Grouping of cablesQuestion 16
1) C1 – Page 24 GN 3
2) C2 – Page 142 GN 3
3) C1 – Page 24 GN 3
4) C3 – 701.410.3 BS7671Question 17
Page 14 GN 3
The customer / client / owner
The InspectorQuestion 18
Regulation 412 BS7671
Items – Fans, fixed appliances, cables
Locations – All locations such as bathrooms kitchens and areas with risk of mechanical demage
Inspections – Condition of cables, Double Insulation up to terminals, connections, Reinforced InsulationQuestion 19
Page 33 GN 3
Here are just a few examples –
Cable terminations
Barriers and enclosures undamaged and present
Labels and identification
Correct size, type and KA of protective devices
IP codes metQuestion 20
Page 62 GN 3
One coil induces a known voltage in a loop circuit containing the earth electrode under test, the general mass of Earth and other connections with Earth within the installation. The second coil measures the test current.
Question 21
Page 19 & 120 GN 3
Adding to an existing circuit
Alteration to an existing circuit
Replacement of equipment such as accessories or luminairesQuestion 22
Page 109 GN 3
No Load Voltage between 4V and 24V
Question 23
Page 87 GN 3
Educational establishments – 6 months and 5 years
Public houses – 1 year and 5 years
Marinas – 4 months and 1 yearQuestion 24
Page 84 GN 3
Breakages
Wear/deterioration
Signs of overheating
missing parts (covers or screws)
Loose fixingsQuestion 25
Page 77 GN 3
Initial verification is carried out by an inspection and functional tests of the isolation IT system equipment including the insulation monitoring devices. Testing is required to measure the leakage current of the output circuit of medical IT isolating transformers and measurement of the resistance of the supplementary equipotential bonding.
Question 26
Page 75 GN 3
Every 6 Months
Question 27
Page 65 GN 3 – Ensuring the Voltage never exceeds 50 V)
30mA – 1667 ohms (0.03 x 1667 = 50V)
100 mA – 500 ohms (0.1 x 500 = 50V)
300 mA – 167 ohms (0.3 x 167 = 50V)
500mA – 100 ohms (0.5 x 100 = 50V)Question 28
Page 55 GN 3
Basic separation – Between the electrically separated live conductors and the transformer secondary live conductors
Basic insulation of the separated conductors – Between the electrically separated live conductors and their corresponding exposed-conductive-parts
Basic insulation of any exposed-conductive-parts associated with separated conductors(Test Voltage and Max value for all types – 500V & 1 Mohm)
Question 29
Page 41 GN 3
One lead of the test instrument is connected to the earth terminal at the distribution board via a length of test cable or ‘wandering lead’. The other test lead is used to make contact with the protective conductor at various points on the circuit under test, for example, luminaires, switches, fused connection units, etc.
Question 30
Page 19 GN 3
1)the maximum demand, expressed in amps, kW or kVA (after diversity is taken into account);
2) the number and type of live conductors of the source(s) of energy and of the circuits used in the installation;
3) the type of system earthing used by the installation and any facilities provided by the distributor for the user;
4) the nominal voltage(s) and its characteristics including harmonic distortion;
5) the nature of the current and supply frequency;
6) the prospective short-circuit current at the origin of the installation;
7) the earth fault loop impedance (Ze) of that part of the system external to the installation; and
8) the type and rating of the overcurrent protective device(s) acting at the origin of the installation.
- Review
- Answered
- Correct
- Incorrect
-
Question 1 of 30
1. Question
-
Question 2 of 30
2. Question
-
Question 3 of 30
3. Question
-
Question 4 of 30
4. Question
-
Question 5 of 30
5. Question
-
Question 6 of 30
6. Question
-
Question 7 of 30
7. Question
-
Question 8 of 30
8. Question
-
Question 9 of 30
9. Question
-
Question 10 of 30
10. Question
-
Question 11 of 30
11. Question
-
Question 12 of 30
12. Question
-
Question 13 of 30
13. Question
-
Question 14 of 30
14. Question
-
Question 15 of 30
15. Question
-
Question 16 of 30
16. Question
-
Question 17 of 30
17. Question
-
Question 18 of 30
18. Question
-
Question 19 of 30
19. Question
-
Question 20 of 30
20. Question
-
Question 21 of 30
21. Question
-
Question 22 of 30
22. Question
-
Question 23 of 30
23. Question
-
Question 24 of 30
24. Question
-
Question 25 of 30
25. Question
-
Question 26 of 30
26. Question
-
Question 27 of 30
27. Question
-
Question 28 of 30
28. Question
-
Question 29 of 30
29. Question
-
Question 30 of 30
30. Question